Watts to Amps Calculator

P → I for DC, single-phase and three-phase, pf explicit.

The formula behind it

DC: I = P ÷ V; single-phase: I = P ÷ (V × pf); three-phase: I = P ÷ (√3 × V_L × pf)
pf
power factor (0–1) — real work per unit of apparent power; 1.0 for pure resistance
√3
the three-phase line-current factor (~1.732)

Converting power to current needs the system stated: DC divides by voltage alone; single-phase AC divides by voltage × power factor; three-phase divides by √3 × line voltage × pf. The power factor accounts for reactance — a 0.8 pf motor draws 25% more current than a resistive heater of the same wattage, which is why cable sizing must use the true current. This calculator never assumes a phase or pf; you select them.

How to use this calculator

  1. 1

    Enter the power in watts or kilowatts (either field works).

  2. 2

    Select the system: DC, single-phase AC, or three-phase AC (line-to-line voltage).

  3. 3

    For AC, enter the power factor (1 for resistive loads, nameplate value for motors).

  4. 4

    Press Calculate to see the current in amperes.

Worked examples

Single-phase heater

2,300 W at 230 V, pf 1 → 10 A.

Three-phase motor

10 kW at 400 V, pf 0.8 → 10,000 ÷ (1.732 × 400 × 0.8) = 18.04 A per line.