The formula behind it
DC: P = V × I; single-phase: P = V × I × pf; three-phase: P = √3 × V_L × I × pf- pf
- power factor — the fraction of apparent (VA) power doing real work
Watts from amps multiply by voltage — and for AC, by the power factor. The distinction matters at scale: a three-phase 18 A line at 400 V delivers 12.5 kW at pf 1 but only 10 kW at pf 0.8, which is why utilities bill industrial customers for poor pf. The apparent power (VA) is shown beside the real power so the gap is visible rather than hidden.
How to use this calculator
- 1
Enter the measured current and the supply voltage.
- 2
Select DC, single-phase or three-phase; enter pf for AC systems.
- 3
Press Calculate — real power in W and kW, plus apparent VA.
Worked examples
Kettle
10 A at 230 V, pf 1 → 2,300 W.
Three-phase
20 A at 400 V, pf 0.85 → √3 × 400 × 20 × 0.85 = 11.78 kW.